T4e 20 – 350 kW

£50.00

Wood chip boiler

T4e

User-friendly, compact, economical and safe:

The new T4e from Froling meets all your needs. With the silicon carbide combustion chamber, the
T4e ensures a high level of efficiency (up to 96.3%) with very low emissions. Well-planned use of energysaving EC drives ensures extremely low energy consumption.

Thanks to its modular construction and compact dimensions, the Froling T4e is particularly easy to position and install. The entire boiler comes fully assembled, electrically wired and tested.

Particular attention was paid to energy efficiency, durability and stability during the development of the T4e. The T4e consumes very little electricity during operation, keeping the operating costs
down. This priority was clearly confirmed when the boiler was awarded the EnergieGenie prize.

Description

Individual control unit of the heating system

Lambdatronic 3200 control unit

Fröling provides a future-oriented Lambdatronic 3200 and a new 7“ touch display. Intelligent control management makes it possible to connect up to 18 heating circuits, up to 4 storage tanks and up to 8 hot water storage tanks. The control unit ensures that the operating statuses are clearly shown. The menu structure is ideally organised to allow easy operation. All essential functions can be selected by simply pressing icons on the large colour display.

Advantages:

  • Precise combustion control by a Lambda control using a Lambda probe
  • Connection for up to 18 heating circuits, 8 water heaters and up to 4 storage tank management systems
  • Integration capability for a solar panel system
  • LED frame for status display with illuminated presence detection
  • Simple and intuitive operation
  • Various smart home options (such as Loxone)
  • Remote control from the living room (remote control 3200 and RGB 3200 Touch) or via Internet (froeling-connect.com)
 
Keep track of everything with the Froling App

The Froling App allows you to check and control your Froling boiler online from
anywhere, at any time. You can read and modify the main status information and settings easily and conveniently online. You can also specify which status messages you want to be informed about via SMS or e-mail (e.g. when the ash box is to be emptied or in the event of a fault message).
The app is available in the Android Play Store and iOS App Store.

Advantages

  • Simple and intuitive operation of the boiler
  • Status information can be called up and changed within seconds
  • Individual naming of the heating circuits
  • Changes of status are notified directly to the user (e.g. via
    e-mail or push notifications)
  • No additional hardware required (such as an Internet gateway)

Smart Home

Loxone

Combine your Froling heating system with the Loxone Miniserver and the new Froling Extension and implement individual boiler control on the basis of the single room control of the Loxone Smart Home.

Modbus

Via the Froling modbus interface, the system can be integrated
into a building management system.

 

Download brochures

Technical Details

T4e

Technical specifications

Technical specifications – T4e 20 25 30 35 45 50 60 80 > 80
Nominal output   [kW] 19,9 25,1 30 35 45 49,9 60 80
Thermal output range   [kW] 5,95 – 19,9 7,51 – 25,1 9 – 30 10,5 – 35 13,5 – 45 14,9 – 49,9 18 – 60 24 – 80
Weight of boiler (Including stoker, without water)   [kg] 740 850 1160
Permitted fuel as per EN ISO 172251) Part 2: Wood pellets class A1 / D06 / Part 4: Wood chips class A2 / P16S-P31S
T4e

Dimensions

Dimensions [mm] 20 – 35 45 – 60 < 80
H      Boiler height 1490 1690
B       Boiler width Width without insulation (width required) 640<br>- 640<br>-
B1    Total width with stoker unit 1410 1410
B2    Width of stoker unit 770 770
B4    Width of particle separator/electrostatic precipitator (optional) 165 165
L       Length of boiler 1170 1270
L1     Overall length 1475 1550
L2     Length, back of boiler to stoker connection 690 770
T4e

Operating and maintenance areas

Minimum clearances [mm] 20 25 30 35 45 50 60 80 <80
A   Insulated door to wall 700 700 700 700 700 700 700 800
B   Side of boiler to wall 150 150 150 150 150 150 150 150
C   Back of boiler to wall 500 500 500 500 500 500 500 500
D   Stoker to wall 300 300 300 300 300 300 300 300
E   Maintenance area above the boiler 500 500 500 500 500 500 500 500
Minimum room height 1800 1800 1800 1800 2000 2000 2000 2100